Comparison of Measured and Calculated Heat Transfer Coefficient of External Wall at the Mechanical Engineering Faculty University in Sarajevo Cover Image

Comparison of Measured and Calculated Heat Transfer Coefficient of External Wall at the Mechanical Engineering Faculty University in Sarajevo
Comparison of Measured and Calculated Heat Transfer Coefficient of External Wall at the Mechanical Engineering Faculty University in Sarajevo

Author(s): Nurin Zecevic, Ejub Džaferović, Azrudin Husika
Subject(s): ICT Information and Communications Technologies
Published by: UIKTEN - Association for Information Communication Technology Education and Science
Keywords: building; external walls; heat flow method; heat transfer coefficient;

Summary/Abstract: Aim of the research was measuring the heat transfer coefficient of the external walls at the Mechanical Engineering Faculty building with heat flow method, in order to obtain the real value of heat transfer coefficient. After performing the measuring according to the ISO 9869 for in-situ measurement, the average measured heat transfer coefficient was 0.23 W/m2K, which is lower value compared to the calculated one, 0.33 W/m2K, according to the program (KiExpert). Difference between values is the result of limitations in selection of materials and because heat accumulation in building elements is not sufficiently considered in algorithms of the program.

  • Issue Year: 8/2019
  • Issue No: 2
  • Page Range: 417-423
  • Page Count: 7
  • Language: English